Nordland flameproof pendants are for use in locations where the atmosphere is likely to be potentially explosive under normal operating conditions ie. zone 1.

Hydrogen: Not suitable for hydrogen atmospheres.

Constructed to SABS 314 the enclosure is rated for gas groups I, II A, II B.

Application: For use in fiery mines and Surface Industries.





Series 100 and 200 pendants

Body: Cast iron

Lens Ring: Cast iron

Construction: The lens ring and body have a machined flame path on the flanged joints. The 8mm thick glass is cemented into the lens ring and mechanically held in place by a circlip. The glass dome is protected by means of a heavy wire guard. A hinge allows the lens ring to be suspended from the body to relamp. Four countersunk hex head screws hold the ring in place.

Entries: Specify - 1 way or 3 way

Glands: not supplied, must be FLP and to the correct size of cable installed.

Incandescent: E27 Lampholder.

Flashing pendants:
Control Gear Options
1. Xenon lamp, either 10-30V DC or 110 alternatively 220V AC
2. Incandescent flasher 24-80V DC or 110/220V AC
3. Lens colours, Blue, Red, Green or Amber

Mounting: 10mm Diameter threaded blind socket for an eyebolt or plate

Option: LM4 Aluminium in 100 series only. Mounting, lug with 10 mm diameter hole centrally positioned.


Flameproof Apparatus
Enclosures are divided into the following main groups -

Group I For use underground in mines i.e. for use in the presence of methane (fire damp);

Group II For use above ground and subdivided according to their suitability for use in atmospheres containing specific gases and vapours as shown in the following table.

Subgroup
Gas/Vapour
II A Industrial methane Ethyl Methyl ketone
Ammonia methyl acetate
Blastfurnace gas Ethyl acetate
Carbon monoxide n-Propyl acetate
Propane n-Butyl acetate
Butane Amyl acetate
Pentane Chloro-ethylene
Hexane Methanol
Heptane Ethanol
iso-Octane iso-Butanol
Decane n-Butanol
Benzene Amyl alcohol
Xylene Ethyl nitrite
Cyclohexane
Acetone
II B Buta-1:3 diene Ethylone oxide
Ethylene Coal gas (Town gas)
Diethyl ether Coke-oven gas
II C Hydrogen

Industrial methane includes methane mixed with not more than 10% (v/v) of hydrogen.

Town gas may contain not more the 57% (v/v) of hydrogen and not more than 16% (v/v) of carbon monoxide, the remainder being a mixture of paraffin hydrocarbons and inert gas.